# 浪涌电流

**浪涌电流**，也称输入浪涌电流或开机浪涌，是电气设备在刚接通电源时瞬间抽取的大电流，通常可达设备稳态电流的数倍<sup>[1](https://www.keysight.com/gb/en/assets/3125-1257/application-notes/Methods-for-Characterizing-DC-Inrush-Current.pdf)</sup>。它出现在具有大输入电容的设备中，如DC-DC变换器和开关电源；出现在瞬态阻抗极低的设备中，如电动机；也出现在变压器通电的瞬间<sup>[1](https://www.keysight.com/gb/en/assets/3125-1257/application-notes/Methods-for-Characterizing-DC-Inrush-Current.pdf)</sup>。不受控制的浪涌可能损坏元件、使保护装置跳闸、干扰供电电压，因此大多数电源设备都包含某种形式的浪涌抑制<sup>[1](https://www.keysight.com/gb/en/assets/3125-1257/application-notes/Methods-for-Characterizing-DC-Inrush-Current.pdf)</sup>。

| 关键事实 | 详情 |
|---|---|
| 定义 | 通电瞬间的浪涌电流，可达稳态电流的数倍<sup>[1](https://www.keysight.com/gb/en/assets/3125-1257/application-notes/Methods-for-Characterizing-DC-Inrush-Current.pdf)</sup> |
| 变压器 | 励磁涌流可达额定满载电流的8–12倍，并在10–40个周期内衰减<sup>[2](https://www.emiratestransformer.com/us/en/resources/glossary/inrush-current/)</sup> |
| 电动机 | 浪涌电流可达稳态电流的25倍；NEMA启动器须承受连续电流的10倍<sup>[1](https://www.keysight.com/gb/en/assets/3125-1257/application-notes/Methods-for-Characterizing-DC-Inrush-Current.pdf)</sup><sup> • </sup><sup>[3](https://www.se.com/us/en/faqs/FA235774/)</sup> |
| 主要原因 | 大输入电容和滤波电容的充电、铁芯带剩磁的磁化，以及转子静止时的低阻抗<sup>[4](https://article.murata.com/en-sg/article/what-is-inrush-current)</sup><sup> • </sup><sup>[5](https://www.eaton.com/us/en-us/products/low-voltage-power-distribution-control-systems/switchboards/protecting-step-up-transformers/understanding-transformer-inrush-current.html)</sup> |
| 常见限制器 | 串联在供电线路中的NTC热敏电阻；冷态时电阻高，自热后电阻低<sup>[6](https://www.eaton.com/content/dam/eaton/products/electronic-components/resources/technical/eaton-ntc-thermistors-app-note-elx1247-en.pdf)</sup> |
| 有源替代方案 | 预充电电阻，待电容充电完成后由继电器、晶闸管或MOSFET旁路<sup>[7](https://components.omron.com/eu-en/solutions/relays/high-capacity-relays/inrush-prevention-circuits)</sup><sup> • </sup><sup>[8](https://product.tdk.com/en/techlibrary/applicationnote/howto_ptc-limiter.html)</sup> |
| 保护影响 | 超过微型断路器瞬时脱扣阈值的浪涌会导致误跳闸；B、C、D型断路器可承受逐渐增大的浪涌<sup>[9](https://www.se.com/uk/en/faqs/FA242032/)</sup> |

## 原因

电子设备中的主要原因在于电容充电。当带有大容量平滑电容或去耦电容的设备接通电源时，未充电的电容表现得如同短路，大电流持续流入，直至电容达到其工作电压<sup>[4](https://article.murata.com/en-sg/article/what-is-inrush-current)</sup><sup> • </sup><sup>[8](https://product.tdk.com/en/techlibrary/applicationnote/howto_ptc-limiter.html)</sup>。在开关电源中，用于平滑整流后市电电压的输入滤波电容是浪涌的主要来源<sup>[6](https://www.eaton.com/content/dam/eaton/products/electronic-components/resources/technical/eaton-ntc-thermistors-app-note-elx1247-en.pdf)</sup>。初始电阻低的元件也有贡献：冷态灯丝会抽取大电流，随着温度升高电流下降<sup>[4](https://article.murata.com/en-sg/article/what-is-inrush-current)</sup>。

浪涌事件的规模由两个参数描述：峰值电流，即峰值与稳态值之差；以及脉冲宽度，即电流收敛至稳态所需的时间<sup>[4](https://article.murata.com/en-sg/article/what-is-inrush-current)</sup>。两者都关系到元件的存亡；元件可能因极高的瞬时峰值熔断内部电极而失效，也可能因持续时间较长、幅度中等的浪涌使其升温，最终导致同样的失效<sup>[4](https://article.murata.com/en-sg/article/what-is-inrush-current)</sup>。

## 变压器涌流

变压器涌流是一种磁化现象，而非电容现象。当一次绕组通电时，会在铁芯中感应出磁通。如果铁芯保留有上次通电留下的剩磁，而电压又在使该剩磁增强的周期相位点重新施加，铁芯便会饱和，其有效阻抗骤降，从而产生巨大的电流尖峰<sup>[2](https://www.emiratestransformer.com/us/en/resources/glossary/inrush-current/)</sup><sup> • </sup><sup>[5](https://www.eaton.com/us/en-us/products/low-voltage-power-distribution-control-systems/switchboards/protecting-step-up-transformers/understanding-transformer-inrush-current.html)</sup>。剩磁本身取决于断电时处于磁滞回线的哪个位置；在励磁电流峰值处断开电源，留下的剩磁比在较低电流处断开更大<sup>[5](https://www.eaton.com/us/en-us/products/low-voltage-power-distribution-control-systems/switchboards/protecting-step-up-transformers/understanding-transformer-inrush-current.html)</sup>。

涌流可达额定满载电流的8–12倍，并随着铁芯建立稳态磁通而在10–40个周期内按指数衰减<sup>[2](https://www.emiratestransformer.com/us/en/resources/glossary/inrush-current/)</sup>。对于较小容量设备，经验法则给出：容量至2500 kVA的变压器，涌流约为额定电流的8倍<sup>[10](https://www.idc-online.com/technical_references/pdfs/electrical_engineering/Transformer_Inrush.pdf)</sup>。真正的最大涌流需要三种条件同时满足，而这极不可能：在最大磁通密度处断电、断电前铁芯已被驱至饱和、以及在磁通极性正好相反的精确点重新接通，因此在选择过流保护时通常以实际最大值为依据<sup>[5](https://www.eaton.com/us/en-us/products/low-voltage-power-distribution-control-systems/switchboards/protecting-step-up-transformers/understanding-transformer-inrush-current.html)</sup>。

由于涌流本身无害，却形似故障，保护继电器必须将二者区分开来。现代继电器采用二次谐波制动，利用涌流波形富含谐波的特点，防止通电期间误跳闸<sup>[2](https://www.emiratestransformer.com/us/en/resources/glossary/inrush-current/)</sup>。线圈阻抗也决定了衰减速率：为提升效率而降低绕组电阻，会延长涌流持续时间，这在选择保护装置时必须加以考虑<sup>[5](https://www.eaton.com/us/en-us/products/low-voltage-power-distribution-control-systems/switchboards/protecting-step-up-transformers/understanding-transformer-inrush-current.html)</sup>。

## 电动机浪涌

静止状态下的感应电动机转子未磁化，没有反电动势对抗电源，因此启动时大电流流过转子绕组；随着转子加速、转差减小，反电动势建立，电流随之衰减<sup>[11](https://www.mayfield.energy/technical-articles/motor-and-transformer-inrush-considerations/)</sup>。电动机在接通电源时可抽取其稳态电流的25倍<sup>[1](https://www.keysight.com/gb/en/assets/3125-1257/application-notes/Methods-for-Characterizing-DC-Inrush-Current.pdf)</sup>。

电动机浪涌与变压器涌流在波形和持续时间上有所不同。电动机浪涌的倍数较低，但衰减更慢，历时数秒而非数个周期，其波形主要是基波电流，比富含谐波的变压器瞬态更为对称<sup>[11](https://www.mayfield.energy/technical-articles/motor-and-transformer-inrush-considerations/)</sup>。NEMA的定义将堵转电流——即额定电压下转子被固定不动时抽取的稳态电流——与瞬时峰值浪涌区分开来，后者在第一个半周期内可达堵转值的1.8至2.8倍<sup>[12](https://publications.jrc.ec.europa.eu/repository/bitstream/JRC75411/reqno_jrc75411__eemods_2011_proceedings_online.pdf)</sup>。按照NEMA规定，电动机启动器在浪涌时必须承受其连续电流额定值的10倍；因此额定连续电流为9 A的启动器必须能承受90 A的电动机浪涌<sup>[3](https://www.se.com/us/en/faqs/FA235774/)</sup>。

## 限制方法

**NTC热敏电阻。** 最常见的无源限制器是串联在供电线路中的负温度系数（NTC）热敏电阻，通常紧接在市电EMI滤波器之后<sup>[13](https://my.avnet.com/abacus/solutions/technologies/power/the-design-engineers-guide/how-to-limit-inrush-current/)</sup>。冷态时其高电阻限制浪涌；电流引起的自热随后使其电阻降至低值，不影响正常工作<sup>[6](https://www.eaton.com/content/dam/eaton/products/electronic-components/resources/technical/eaton-ntc-thermistors-app-note-elx1247-en.pdf)</sup><sup> • </sup><sup>[14](https://www.ametherm.com/inrush-current/how-to-stop-inrush-current)</sup>。这使其比固定电阻更高效，后者在稳态下持续耗散功率<sup>[6](https://www.eaton.com/content/dam/eaton/products/electronic-components/resources/technical/eaton-ntc-thermistors-app-note-elx1247-en.pdf)</sup>。该方法也有局限：器件依靠温升工作，因此在宽环境温度范围内性能会有变化；断电后约需60秒冷却，才能限制下一次浪涌；且它不能替代保险丝，短路保护仍需保险丝<sup>[6](https://www.eaton.com/content/dam/eaton/products/electronic-components/resources/technical/eaton-ntc-thermistors-app-note-elx1247-en.pdf)</sup><sup> • </sup><sup>[15](https://electricalflux.com/learn-components/ntc-inrush-current-limiter-sizing-capacitive-loads)</sup>。

**预充电与旁路电路。** 有源电路通过电阻为电容充电，然后将电阻从电路中移除。在基于继电器的预充电方案中，预充电继电器先闭合，使电流流经限流电阻，而主继电器保持断开；待电容充电完成，主继电器闭合、预充电继电器断开，负载经由主电路供电<sup>[7](https://components.omron.com/eu-en/solutions/relays/high-capacity-relays/inrush-prevention-circuits)</sup>。这种RC电路中的充电电流遵循 \( I(t) = (E/R) \cdot e^{-t/(R \cdot C)} \)，因此电阻和所需的预充电时间决定了峰值电流和继电器额定值<sup>[7](https://components.omron.com/eu-en/solutions/relays/high-capacity-relays/inrush-prevention-circuits)</sup>。在车载充电器和工业逆变器的浪涌限制电路中，晶闸管或继电器旁路也会与PTC热敏电阻组合使用；若旁路未能闭合，PTC升温进入高阻态，限制故障电流而不致损坏<sup>[8](https://product.tdk.com/en/techlibrary/applicationnote/howto_ptc-limiter.html)</sup>。基于MOSFET的有源限制器同样将电阻保持在电路中，直至直流母线电压达到目标值的约90%，然后将其旁路以降低稳态损耗<sup>[16](https://diotec.com/en/latest-news.html?file=files%2Fdiotec%2Ffiles%2Fpdf%2Fservice%2Fapplications%2FApp_Note_Power_Supply.pdf&page=3&page_a114=25)</sup>。

**电动机启动设备。** 软启动器使电动机电压逐渐上升，但作为降压设备，它们仍会抽取典型值为电动机满载电流350%至500%的浪涌电流，高于以全压启动电流为基准、仅按电压降低幅度推算出的数值<sup>[17](https://www.se.com/us/en/faqs/FA233948/)</sup>。变频驱动器既能控制启动电流，也能控制转速，且可以更频繁地循环启停而不过热<sup>[17](https://www.se.com/us/en/faqs/FA233948/)</sup>。

## 保护配合与测量

浪涌与过流保护相互作用。如果浪涌超过微型断路器的瞬时脱扣阈值，断路器就会跳闸并中断供电，这种问题称为误跳闸，在电动机和变压器负载中很常见<sup>[9](https://www.se.com/uk/en/faqs/FA242032/)</sup>。断路器的选择可以应对这一问题：B型微型断路器在较低浪涌下跳闸，适合住宅负载；C型可应对商业应用中的中等浪涌；D型可处理重型机械的高浪涌；许多微型断路器还具有延时特性，可容忍短暂浪涌而不跳闸<sup>[9](https://www.se.com/uk/en/faqs/FA242032/)</sup>。

表征浪涌需要捕获高分辨率的浪涌数字化波形，或获得可靠的峰值读数，通常使用高分辨率示波器或高精度数字万用表<sup>[1](https://www.keysight.com/gb/en/assets/3125-1257/application-notes/Methods-for-Characterizing-DC-Inrush-Current.pdf)</sup>。这种测量服务于多项设计目标：保护元件免受热应力、避免LED照明阵列等系统中的断路器跳闸和保险丝熔断、防止数据中心内多台设备同时启动时的电压暂降，以及满足IEC、UL和IEEE准则下适用于电源适配器和电池充电器等产品的浪涌法规限值<sup>[1](https://www.keysight.com/gb/en/assets/3125-1257/application-notes/Methods-for-Characterizing-DC-Inrush-Current.pdf)</sup>。

## References

1. [Methods for Characterizing DC Inrush Current, Keysight application note](https://www.keysight.com/gb/en/assets/3125-1257/application-notes/Methods-for-Characterizing-DC-Inrush-Current.pdf)
2. [Inrush Current, Transformer Glossary, Emirates Transformer](https://www.emiratestransformer.com/us/en/resources/glossary/inrush-current/)
3. [How much inrush current can a Square D NEMA starter handle?, Schneider Electric](https://www.se.com/us/en/faqs/FA235774/)
4. [What is inrush current?, Murata Manufacturing](https://article.murata.com/en-sg/article/what-is-inrush-current)
5. [Practical guide to understanding transformer inrush current, Eaton](https://www.eaton.com/us/en-us/products/low-voltage-power-distribution-control-systems/switchboards/protecting-step-up-transformers/understanding-transformer-inrush-current.html)
6. [NTC thermistors application note, Technical Data ELX1247, Eaton](https://www.eaton.com/content/dam/eaton/products/electronic-components/resources/technical/eaton-ntc-thermistors-app-note-elx1247-en.pdf)
7. [How to choose high-capacity relays for inrush current prevention circuits, Aratas (Omron Components)](https://components.omron.com/eu-en/solutions/relays/high-capacity-relays/inrush-prevention-circuits)
8. [How to use PTC thermistors as current protection, TDK application note](https://product.tdk.com/en/techlibrary/applicationnote/howto_ptc-limiter.html)
9. [How does a high inrush current affect the Acti9 MCBs?, Schneider Electric](https://www.se.com/uk/en/faqs/FA242032/)
10. [Transformer Inrush, IDC Technologies technical reference](https://www.idc-online.com/technical_references/pdfs/electrical_engineering/Transformer_Inrush.pdf)
11. [Motor and Transformer Inrush Considerations, Mayfield Renewables](https://www.mayfield.energy/technical-articles/motor-and-transformer-inrush-considerations/)
12. [Locked rotor current and NEMA inrush definitions, JRC75411, European Commission Joint Research Centre](https://publications.jrc.ec.europa.eu/repository/bitstream/JRC75411/reqno_jrc75411__eemods_2011_proceedings_online.pdf)
13. [How to limit inrush current: the design engineer's guide, Avnet Abacus](https://my.avnet.com/abacus/solutions/technologies/power/the-design-engineers-guide/how-to-limit-inrush-current/)
14. [How to stop inrush current, Ametherm](https://www.ametherm.com/inrush-current/how-to-stop-inrush-current)
15. [How to size an NTC inrush current limiter for capacitive loads, ElectricalFlux](https://electricalflux.com/learn-components/ntc-inrush-current-limiter-sizing-capacitive-loads)
16. [Power supplies application note: active inrush current limitation, Diotec Semiconductor](https://diotec.com/en/latest-news.html?file=files%2Fdiotec%2Ffiles%2Fpdf%2Fservice%2Fapplications%2FApp_Note_Power_Supply.pdf&page=3&page_a114=25)
17. [Differences between variable frequency drives and soft starters, Schneider Electric](https://www.se.com/us/en/faqs/FA233948/)

---
*Initially written Sep 17, 2026 · Reviewed: Oct 15, 2026 · Edited: Oct 15, 2026 · Last review: Oct 15, 2026*

Topic: 物质世界与数学 › 物理学 › 经典物理学 › Electromagnetism › Electromagnetic quantities and history › Electromagnetic quantities › Electric charge and current quantities